VEGA VEGAMET 407 AFT User Manual

Page 6

Advertising
background image

6

VEGAMET 407 AF/AFT

-

Feed supply voltage. The voltage must comply
with the figure stated on the wiring diagram.

-

Adjust changeover switch on the back of the
instrument or on the front plate to the desired
current output range 0 … 20 mA or 4 … 20 mA

-

turn potentiometer for integration time complete-
ly anti-clockwise

-

potentiometer for full adjustment must be turned
clockwise by 22 turns

-

Carry out adjustment as follows

Adjustment

The full or empty adjustment is carried out by a
spindle potentiometer. Overwinding is avoided by
the slide clutch. In practice three different methods
are possible for empty / full adjustment:

a) Level in the vessel can be filled to the

required min. level (= 0 %) and max. level
(= 100 %)

Empty adjustment
-

Reduce product to required min. level.

-

Adjust with potentiometer for empty adjustment
the indication of the instrument to 0 %.

Full adjustment
-

Increase product to required max. level.

-

Adjust with potentiometer for full adjustment the
indication of the instrument to 100 %.

Integration time
-

Adjust potentiometer for integration time to
required value (see page 2).

b) Level in the vessel can be filled to the

required min. level (= 0 %), but only to a max.
level < 100 %

Empty adjustment
-

Reduce product to required min. level.

-

Adjust with potentiometer for empty adjustment
the indication of the instrument to 0 %.

Full adjustment
-

Increase product to max. possible level and
dipcheck (e.g. 80 %)

-

Adjust with the potentiometer for full adjustment
the indication of the instrument to the checked
value.

Integration time
-

Adjust potentiometer for integration time to
required value (see page 2).

c) Level in the vessel can only be reduced to a

min. level > 0 % and to a max. level

100 %

Empty adjustment
-

Reduce product to min. possible level and
dipcheck (e.g. 20 %)

-

Adjust with the potentiometer for empty adjust-
ment the indication of the instrument to the
checked value.

Full adjustment
-

Increase level to max. possible level and
dipcheck (e.g. 60 %)

-

Calculate indication value to be adjusted:
max. level minus min. level = indicating value to
be adjusted.
in the example: 60 % - 20 % = 40 %

-

Set with the potentiometer for full adjustment the
indication of the instrument to the calculated
value (in the example 40 %).

-

Set with the potentiometer for empty adjustment
the indication of the instrument to the actual
level (max. level in the example 60 %).

Integration time
-

Adjust with potentiometer for integration time to
required value.

407 AF

100

0

50

%

tj

0

VEGAMET

Start-up

Fixing screw

Fixing screw

Mains control lamp

Indication instrument

Signal lamp

Potentiometer
for full adjustment

Potentiometer
for empty adjustment

Potentiometer
for integration time

Advertising