2 connection instructions, 3 wiring plan, Not intrinsically safe input – VEGA VEGATRENN 547 V Ex User Manual

Page 10: Intrinsically safe output

Advertising
background image

10

VEGATRENN 547 V Ex

3.3 Wiring plan

2

6

12

20

28

24

22

10

16

18

30

32

d b z

1 +

2 –

3 +

4 –

1 +

2 –

L (+)
N (–)

26

14

+

8

4

3 +

4 –

Power
supply

VBUS-
connection
of signal
conditioning
instrument

VBUS-
sensor 2

VBUS-
sensor 2

3.2 Connection instructions

Not intrinsically safe input

The not intrinsically safe input of the Ex-
separator is connected via a standard two-
wire line with a signal conditioning instrument.
If electromagnetic interferences have to be
expected, screened cable should be used.
The screen must only be earthed at one end
of the signal conditioning instrument.

Intrinsically safe output

The wiring of the intrinsically safe outputs of
the Ex-separator with the sensors must meet
with the valid installation regulations. E.g. the
DIN-regulations prescribe that the connection
lines between Ex-separator and sensors must
be marked on the entire length. For coverings
light blue must be used as colour.

If electromagnetic interferences must be
expected, screened cable must be used. The
screen must only be earthed at one sensor.

Electrical connection

VBUS-
sensor 1

VBUS-
sensor 1

Advertising