2 technical data – VEGA VEGATRENN 547 V Ex User Manual

Page 5

Advertising
background image

VEGATRENN 547 V Ex

5

Product description

1.2 Technical data

Power supply

Operating voltage

U

nom

= 24 V AC (20 … 53 V), 50/60 Hz
= 24 V DC (20 … 72 V)

Power consumption

approx. 13 W, approx. 18 VA

Fuse

1 A, slow-blow

Signal conditioning instrument circuit

For connection to

signal conditioning instrument VEGAMET 514 V,
515 V or
EV-card of VEGALOG 571

Input voltage

U

nom

= 25 V DC with VEGAMET
= 24 V DC with EV-card VEGALOG

The signal conditioning instrument circuit must only be connected to instruments with an
operating voltage less than 250 V.

Sensor circuit

Number

2 sensor circuits (both 2 ib-circuits)

Sensors

Ultrasonic sensors

VEGASON 83 … 87 FV/GV Ex or Ex0,
radar sensors VEGAPULS 81 F/D Ex or Ex0

Voltage

approx. 17 V DC at 85 mA

Current limitation

electronically at approx. 85 mA, shortcircuit-proof

Connection line per sensor

4-wire (standard line) *

)

Resistance per conductor

max. 7,5

Line length

max. 500 m

Sensor circuits, Ex-technical data

Classification

[EEx ib] IIB

Max. values (per sensor circuit)
- voltage

U

O

20,05 V

- current

I

O

103 mA

- eff
iciency

P

O

2,05 W

Characteristics

linear

Max. permissible outer inductance L

a

0,7 mH

Max. permissible outer capacitance C

a

296 nF

The intrinsically safe sensor current circuits are reliably galvanically isolated from the not
intrinsically safe circuits and supply up to a peak value of the nominal voltage of 375 V.

Indicating elements

LED in front plate

green on: operating voltage on

*

)

screened cable is recommended for electromagnetic interferences.

Advertising