6 enquiry for the software version, 7 error message from vegascan 850 – VEGA VEGASCAN 850 VEGA-ASCII signal output User Manual

Page 15

Advertising
background image

VEGA-ASCII signal output VEGASCAN 850

15

Address

End

Identifier VEGASCAN Reserve

Enquiry

identification

Number of bytes

1

1

2

17

2

Range (ASCII)

=

0..9

00

Answer text

CRLF

Example

=

2

00

VEGASCAN850 V2.17

CRLF

Address

End

Identifier VEGASCAN Reserve

Enquiry

identification

Number of bytes

1

1

2

13

1

Range (ASCII)

%

0..9

00

READ VERSION

CR

Example

%

2

00

READ VERSION

CR

Enquiry of measured values

3.7 Error message from VEGASCAN 850

If an enquiry was not understood correctly by VEGASCAN 850 or the enquiry was transferred
incorrectly, VEGASCAN sends an error message.

Error text

Meaning

"ERROR 5“

- Identifier unknown
- Telegram incomplete

"ERROR 6“

Telegram cannot be evaluated

3.6 Enquiry for the software version

With this enquiry, the software version in VEGASCAN 850 can be identified.

Answer from VEGASCAN 850

Start character: S1 = 1 character "=“
Address: Adr = 1 character VEGASCAN 850 address
Reserve: 2 characters here "00“
Answer: 17 characters text
Total length of the telegram: 23 characters

Telegram from processing system to VEGASCAN 850

Identifier: 1 character, "v“ ("V“)
Call up: 13 characters " READ VERSION“ (for READ and for VERSION 1 blank character each)
End identification: 1 character Chr (13) = CR = Carriage Return
Total length of the telegram: 18 characters

Advertising