3 enquiry of measured values, 1 enquiry as single value – VEGA VEGASCAN 850 VEGA-ASCII signal output User Manual
Page 5
VEGA-ASCII signal output VEGASCAN 850
5
Enquiry of measured values
3 Enquiry of measured values
3.1 Enquiry as single value
Low resolution
This telegram reads a DCS value out of VEGASCAN 850.
Answer from VEGASCAN 850
Start character: S1 = 1 character "=“
Start character: S2 = 1 character "#“
Total length of the telegram: 12 or 13 characters
Telegram from processing system to VEGASCAN 850
Identifier: 1 character, "%“
End identification: 1 character Chr (13) = CR = Carriage Return
Total length of the telegram: 5 characters
1 repetition
1 2 3 4 5 6
3 positions in front of the comma
1 decimal point
1 position after the comma
"-“ with negative values
" " with positive values
valid measured value
1 2 3 4 5
‘FAULT’
Fault
DCS
DCS
End
S1
no.
S2
value2
identification
Number of bytes
1
3
1
5-6
2
Range (ASCII)
=
001..060
#
DCS value or
fault
%CR
Example
=
001
#
-067.3
%CR
DCS
End
Identifier
number
identification
Number of bytes
1
3
1
Range (ASCII)
%
001..060
CR
Example
%
001
CR