VEGA-ASCII signal output VEGASCAN 850

3

With the adjustment software VEGA Visual
Operating (VVO), the configuration of the
VEGA-ASCII interface can be carried out on
VEGASCAN 850. Provide a connection be-
tween PC with VVO and VEGASCAN 850 with
the RS 232 interface cable. The following
illustration is displayed on the PC after
switching on VEGASCAN 850 and starting
VVO.

• Click to "

Configuration“, then to "Measuring

system“, in the next window "Configuration
measuring system“ click to "

Communica-

tion.

Then the window "

Configuration ASCII proto-

col“ opens.

Here, you select the protocol mode (4 digits/
low resolution or 6 digits/high resolution). For
the baud rate (300 … 38400), you make sure
that the rate is set to the same value as the
other BUS participants. For the BUS ad-
dress, settings 1 to 9 are permitted.

• After the configuration settings, click to

"

Save“, then to "Quit“. In the window "Con-

figuration measuring system“ click again to
"

Quit“.

BUS termination

(only with RS 485 interface)

When connecting VEGASCAN to the begin-
ning or end of a bus chain, the instrument
has to be terminated. Set the slide switch
(beside the field bus terminal) to position
"on“.

After setting up the VEGA-ASCII interface,
provide the connection with the bus. In case
of correct communication, the green LED
marked "BA“ in the front plate of VEGASCAN
lights.