5 connecting to power supply, 1 preparing the connection, 2 wiring plan – VEGA VEGATOR 256C User Manual

Page 10

Advertising
background image

5 Connecting to power supply

5.1 Preparing the connection

Always keep in mind the following safety instructions:

l

Connect only in the complete absence of line voltage

l

If overvoltage surges are expected, overvoltage arresters

should be installed

Tip:

We recommend VEGA overvoltage arresters B61-300 (power

supply VEGATOR 256C) and B62-36G (sensor supply).

You can find detailed information on the power supply in

chapter "Technical data" in the "Supplement".

Power supply of VEGATOR 256C is connected with standard

cable according to the national installation standards.
Standard two-wire cable without screening can be used to

connect sensors. If electromagnetic interference is expected,

screened cable must be used.

From a cable length of 50 m use one cable for each signal

conditioning instrument.
If you want to use a common cable, the min. and max. cables

must be screened. The screen must be connected to ground

on both sides.

5.2 Wiring plan

0

10

8

7

6

5

4

N

L1

3

2

1

max.

min.

1

2

3

4

Fig. 3: Level detection

1

Supply

2

Relay output

3

Mass

4

max.

Note safety instructions

Select power supply

Selecting connection cable

Cable screening and ground-

ing

Level detection

10

VEGATOR 256C - Signal conditioning instrument

Connecting to power supply

23409

-EN
-070316