VEGA VEGATOR 256C User Manual

Page 14

Advertising
background image

l

at first, connect only the ground and max. electrode to

VEGATOR 256C (terminal 2 and 3)

l

Connecting the signal conditioning instrument to voltage

supply

l

Turn potentiometer (2) to position 0

l

Fill the vessel until the max. probe is covered approx. 1 cm

by the product

l

Turn potentiometer (2) slowly clockwise until the yellow

LED extinguishes

l

Connect min. electrode to terminal 1 of VEGATOR 256C

The switching sensitivity of the signal conditioning instrument

is now adapted to the conductivity of the product, i.e. the relay

output deenergises with max. level and the yellow control lamp

extinguishes.
This switching condition remains until the level falls below the

position of the min. electrode, i.e. the relay output energizes at

min. level and the yellow control lamp lights.
The relay output deenergises again when the max. level is

reached.

Pump control (min./max.)

14

VEGATOR 256C - Signal conditioning instrument