VEGA VEGATOR 256C User Manual
Page 14
l
at first, connect only the ground and max. electrode to
VEGATOR 256C (terminal 2 and 3)
l
Connecting the signal conditioning instrument to voltage
supply
l
Turn potentiometer (2) to position 0
l
Fill the vessel until the max. probe is covered approx. 1 cm
by the product
l
Turn potentiometer (2) slowly clockwise until the yellow
LED extinguishes
l
Connect min. electrode to terminal 1 of VEGATOR 256C
The switching sensitivity of the signal conditioning instrument
is now adapted to the conductivity of the product, i.e. the relay
output deenergises with max. level and the yellow control lamp
extinguishes.
This switching condition remains until the level falls below the
position of the min. electrode, i.e. the relay output energizes at
min. level and the yellow control lamp lights.
The relay output deenergises again when the max. level is
reached.