10.2 Information on Profibus PA

Instrument master file
The instrument master file (GSD) contains the characteristic data of the Profibus PA instrument.
These data are, e.g. the permissible transmission rates as well as information on diagnostics values
and the format of the measured value outputted by the PA instrument.

A bitmap file is also provided for the Profibus network planning tool. This file is installed automatically
when the GSD file is integrated. The bitmap file is used for symbolic indication of the PA instrument in
the configuration tool.

Ident number
Each Profibus instrument gets an unambiguous ident number (ID number) from the Profibus user
organisation (PNO). This ID number is also included in the name of the GSD file. For VEGABAR 61
the ID number is 0 x 076F(hex) and the GSD file BR__076F.GSD. As an option to this manufacturer-
specific GSD file, PNO provides also a general so-called profile-specific GSD file. For VEGABAR 61
you have to use the general GSD file PA139701.GSD. If the general GSD file is used, the sensor
must be set to the profile-specific ident number via the DTM software. By default, the sensor operates
with the manufacturer-specific ID number.

Note:
When using the profile-specific GSD file, the PA-OUT value as well as
the temperature value are transmitted to the PLC (see block diagram
"C

yclical data traffic").

Cyclical data traffic
The master class 1 (e.g. PLC) cyclically reads out measured values from the sensor during operation.
The below block diagram below shows which data can be accessed by the PLC.

VEGABAR

61 • Profibus PA

63

10 Supplement

28251

-

EN