PA-OUT value of the FB1 after scaling

l

Temperature

-

PA-OUT value of the FB2 after scaling

l

Additional Cyclic Value

-

Additional cyclical value (depending on the source)

l

Free Place

-

This module must be used if a value should not be used in the data telegram of the cyclical data
traffic (e.g. replacement of the temperature and Additional Cyclic Value)

Max. three modules can be active. By means of the configuration software of the Profibus master,
you can determine the configuration of the cyclical data telegram with these modules. The procedure
depends on the respective configuration software.

Tip:
The modules are available in two versions:

l

Short for Profibus master supporting only one "Identifier Format"
byte, e.g. Allen Bradley

l

Long for Profibus master only supporting the "Identifier Format"
byte, e.g. Siemens S7-300/400

Examples of telegram configuration
In the following you will see how the modules can be combined and how the appendant data telegram
is structured.

Example 1 (standard setting) with pressure value, temperature value and additional cyclical value:

l

AI (PA-OUT)

l

Temperature

l

Additional Cyclic Value

Byte-No.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Format

Value

IEEE-754-

Flieskommazahl

PA-OUT

(FB1)

Status

Status

(FB1)

IEEE-754-

Flieskommazahl

Temperature

(FB2)

IEEE-754-

Flieskommazahl

Additional Cyclic

Value

Status

Status

(FB2)

Status

Status

Fig. 31: Telegram configuration example 1

Example 2 with pressure value and temperature value without additional cyclical value:

l

AI (PA-OUT)

l

Temperature

l

Free Place

VEGABAR

61 • Profibus PA

65

10 Supplement

28251

-