Setup – VEGA D80 Hydrostatic pressure transmitters User Manual

Page 29

Advertising
background image

Pressure transmitter D80

29

Setup

1.2.3.1.1

1.2.3.1.2

Note:

After adjustment of a parameter, push "

ENTER" and then "SEND".

Confirm the message to switch over to manual operation with "

OK".

Confirm the message to reset to automatic operation also with "

OK".

Only then will the adjustment be stored in the sensor and take effect.

Menu windows are displayed but not
supported by the sensor.
Saving of adjustments carried out here is
therefore not possible.

1.4.3.1.3

1.4.3.1.2

Low:

In case of failure, current output
goes to 22 mA

High:

In case of failure, current output
goes to < 3.6 mA

1.4.3.2

1.4.3.1

}

Off
On
Not used
None
Unknown
Special

Sensor signals measured values only on
request
Sensor signals measured values
unrequested

Choice is not supported

1.4.3.2.3

1.4.3.2.4

Leave the Burst-mode in
OFF position

Choice is not supported

1.2.3.1.1.1

1.2.3.1.2.1

1.4.3.1.3

1.4.3.1.3.1

Generic: D84
Current applied
process value:

97.112

mbar

1 Set as 4 mA value
2 Read new value
3 Leave as found

ABORTENTER

Generic: D84
Current applied
prosess value :96.262
mbar

1 Set as 20 mA value
2 Read new value
3 Leave as found

ABORT ENTER

Generic: D84
Choose analog output
level

1 4 mA
2 20 mA
3 Other
4 End

ABORTENTER

Generic: D84
WARN - Loop should be
removed from
automatic control

ABORT

OK

Generic: D84
Set the:

1 4 mA
2 20 mA
3 Exit

ABORT ENTER

Generic: D84
Apply new 20 mA input

ABORT

OK

Generic: D84
Current applied
process value: 95.703
mbar

1 Set as 20 mA value
2 Read new value
3 Leave as found

ABORT ENTER

Generic: D84
Set the:

1 4 mA
2 20 mA
3 EXIT

ABORT ENTER

Generic: D84
Apply new 4 mA input

ABORT OK

Generic: D84
Current applied
process value: 96.549
mbar

1 Set as 4 mA value
2 Read new value
3 Leave as found

ABORT ENTER

Generic: D84
AO Alrm typ
Lo

EXIT

Generic: D84
HART output

1 Poll addr

0

2 Num req preams 5
3 Burst mode

Off

4 Burst option

HELP SAVE

HOME

Generic: D84
Analog output

1 AO1

19.920 mA

2 AO Alrm typ
3 Loop test
4 D/A trim
5 Scaled D/A trim

HELP SAVE

HOME

Generic: D84
Fld dev output is
fixed at 4.000 mA

ABBR. OK

Generic: D84
Burst mode
Off

Off
On
Not Used
None

ESC

ENTER

Generic: D84
Burst option
*********

PV
% range/current
Process vars/crnt

HELP

ESC

ENTER