VEGA D80 Hydrostatic pressure transmitters User Manual

Page 32

Advertising
background image

32

Pressure transmitter D80

• Confirm the adjustment with "

OK" and after

saving you are again in the initial menu.

Setup

Note:

When connecting the adjustment software
(VVO) to a sensor from which data has al-
ready been saved, you are asked if the
saved data should be transferred to the
sensor or if you want to transfer the sensor
data to the database of VVO (the available
data of the current sensor will be
overwritten).

If you don’t get communication with the sen-
sor, check the following:
- Is the sensor being supplied with sufficient

voltage (min. 12 V)?

- When VEGACONNECT 2 is connected to

the signal cable, is the load resistance
250 … 350

?

Configuration

• Choose the menu "

Configuration/Measuring

system", to get further information on the
sensor type, the software version of the
sensor, measuring unit, the measurement
loop designation etc.

• Click to "

Quit".

• Click to the menu "

Configuration/Measure-

ment loop/Modify". This is the first step for
the sensor setup.

In the menu "

Modify meas. loop configuration"

you can give a name (e.g. vessel 10) and a
measurement loop description (e.g. cleaning
detergent) to the measurement loop instead
of the sensor number.

• Now enter in this menu whether a level, a

distance or a gauge should be measured.

Advertising