1 product description, 1 function and configuration, 2 approvals – VEGA VEGASEL 643 User Manual

Page 3: Product description, Function, Configuration, Whg-approval, vbf-approval, Ce-conformity, Vegasel 643 3, See „1.4 technical data

Advertising
background image

VEGASEL 643

3

Product description

1 Product description

1.1 Function and configuration

VEGASEL 643 auxiliary level switch is a build-in instru-
ment with terminal socket, suitable for carrier rail
mounting (DIN 46 277). Together with a sensor or a

VEGAMET… signal conditioning instrument it is used
for level detection.

Typical applications are two-point controls, e.g. pump
controls (ON/OFF) and monitoring functions such as

overfill protection and protection against dry running of
pumps.

The auxiliary level switch is provided with two passive
inputs, a current and a voltage input as well as addi-

tionally with an active current input. Hence VEGASEL
643 can be connected for control either with a
VEGAMET… or a sensor (4 … 20 mA).

Function

VEGASEL 643, controlled by a VEGAMET…

- The continuous current or voltage course of the

VEGAMET… signal processing instrument is
processed into a switching command.

Fig. 1.2 VEGASEL 643 with sensor

p

p

Fig. 1.1 VEGASEL 643 on a VEGAMET

1

2

4

3

5

6

7

8

9

10 11 12 13 14

on

VEGAMET 602EX

%

50

0

100

!

1

2

4

3

5

6

7

8

9

10 11 12 13 14

on

max.

min.

VEGASEL 643

+

+

6 5

+

+

3 5

0/4 … 20 mA

or

0 … 10 V

1

2

4

3

5

6

7

8

9

10 11 12 13 14

on

max.

min.

VEGASEL 643

+

+

6 5

+

+

3 5

Sensor

(4 … 20 mA)

VEGASEL 643 with a 4 … 20 mA sensor
- VEGASEL 643 auxiliary level switch powers via the

active current input the sensors and processes its

continuous 4 … 20 mA current signal into a switch-
ing command.

In both cases a relay output is available for process-
ing.

Configuration

With a VEGASEL 643 an available measuring system,
consisting of sensor and VEGAMET signal condition-
ing instrument can be extended by a level detection.

Or an own measuring system can be created with a
4 … 20 mA sensor.

1.2 Approvals

If measuring systems are created according to the
following approvals, the respective legal documents
and their regulations have to be observed. These

documents are supplied with the respective measur-
ing system.

WHG-approval, VbF-approval

VEGASEL 643 auxiliary level switch together with a
measuring system (sensor and VEGAMET) as part of
an overfill protection acc. to WHG (test certificate

applied) or acc. to the regulations for combustible
liquids (test certificate applied).

CE-conformity

see „1.4 Technical data“.