5

Product description

Input 3

1 voltage input

Kind of input

passive two-wire input analog

Range

0/2 … 10 V DC

Inner resistor

Ri

100 k

Application

direct connection to active voltage output of
e.g. VEGAMET 601, 602 Ex

Switching threshold

adjustable via coded key

Min. hysteresis

1 %

Temperature error

0,05 %/10 K of range

Switch point error

0,5 % of adjusted switch point

Connection cable

2-wire (standard line)

Resistor per conductor

max. 100

Electrical connection

Screw terminal

max. 1,5 mm

2

Electrical protective measures

Protection
- instrument

IP 30

- terminal socket

IP 20

Protection

II

Overvoltage category

II

Mechanical data

Series

module instrument with terminal socket incl.
transparent cover, cover of the sensor terminals,
coded pin, two connection bridges

Mounting

carrier rail mounting acc. to DIN 46 277, Bl. 3

Dimensions unassembled

W = 36 mm, H = 118,5 mm, D = 134 mm

Weight

appr. 170 g

Ambient conditions

Permissible ambient temperature

-20

°

C … +60

°

C

Storage and transport temperature

-40

°

C … +70

°

C

Relay output

Number

1 output

Contact

1 spdt (open 12 - 13, closed 12 - 14)

AgCdO and Au plated

Turn-on voltage

min. 10 mV DC
max. 250 V AC, 60 V DC

Switching current

min. 10

µ

A DC

max. 2 A AC, 1 A DC

Breaking capacity

max. 125 VA, 54 W

Indicating elements

LED in front plate

green on: operating voltage on
yellow on: relay energized

Functions

Mode

overfill protection (A)
protection against dry running of pumps (B)

Adjustments of the inputs

0 … 20 mA or 4 … 20 mA

0 … 10 V or 2 … 10 V