3 types and versions, 4 technical data and dimensions – VEGA VEGASEL 643 User Manual

Page 4

Advertising
background image

4

VEGASEL 643

Product description

1.3 Types and versions

VEGASEL 643

Two-point auxiliary level switch with selectable mode; mode A (overfill

protection) or mode B (protection against dry running of pumps)
adjustable switching hysteresis
Inputs:

- passive current input 0/4 … 20 mA
- active current input (connections of a sensor

4 … 20 mA)

- passive voltage input 0/2 … 10 V

Outputs:

1 relay (spdt)

Approvals:

as part of an overfill protection acc. to WHG and
VbF

Application:

level detection, overfill protection,

protection against dry running of pumps

off

on

Level

Time t

Fig. 1.2 Two-point auxiliary level switch

VEGASEL 643

Min.

Max.

1.4 Technical data and dimensions

General data

Power supply

Operating voltage

20 … 250 V AC, 50/60 Hz

20 … 72 V DC

Power consumption

max. 1,7 W (4,5 VA)

Fuse

T 1 A, 250 V

Measuring data inputs

Input 1

1 current input

Kind of input

active two-wire input analog

Range

4 … 20 mA

Application

connection of sensors (4 … 20 mA)

Sensor supply voltage

16 … 24 V DC

Switching threshold

adjustable via coded key

Min. hysteresis

1 %

Current limitation

appr. 25 mA, permanently shortcircuit proof

Temperature error

0,05 %/10 K of range

Switch point error

0,5 % of adjusted switch point

Connection cable

2 wire (standard line)

Resistor per conductor

max. 35

Interlock diode

for connection of a measuring instrument
max. load 15

Input 2

1 additional current input

Kind of input

passive two-wire input analog

Range

0/4 … 20 mA

Inner resistor

Ri = 50

Application

direct connection to active current output of e.g.
VEGAMET 601, 602 Ex

Switching threshold

adjustable via coded key

Min. hysteresis

1 %

Temperature error

0,05 %/10 K of range

Switch point error

0,5 % of adjusted switch point

Advertising