Adjustment example 1 – VEGA VEGAMET 602 User Manual

Page 16

Advertising
background image

16

VEGAMET 601, 602

Setup

0 %

100 %

Capacitive
electrodes

Hydrostatic pressure
transmitter

Process pressure
transmitter

Procedure:

• First of all, turn the potentiometer full adjust-

ment (1) approx. 22 revolutions clockwise.

• Fill the vessel to the requested minimum

level.

• Set with the potentiometer empty adjust-

ment (2) the display of the connected
measuring instrument to 0.0 V, this corre-
sponds to 0 %.

• Fill the vessel to the requested max. level.
• Set with the potentiometer full adjustment

(1) the display of the connected measuring
instrument to 10.0 V by turning anticlock-
wise, this corresponds to 100 %.

• The signal conditioning instrument is ad-

justed and ready for operation
Please cover with the transparent cover
(14).

0/4
0

20 mA
10 V

100 %

0 %

Level

Adjustment example 1

The vessel can be emptied to min. level and
filled to max. level.
Sensor:
- vertically mounted capacitive measuring

probe

- hydrostatic pressure transmitter
- process pressure transmitter