Set-up

5.1

Indication and operating elements

5.2

Input signal

The VEGADIS 171 A is standard for input signals
0/4 … 20 mA.

For other input signals the VEGADIS must be modified
acc. to the following description:

Input signal 0/1 … 5 V

• remove front pane
• R10

unsolder 100 Ohm

• R10

solder 68 K1 1 %

• R11

unsolder 0 Ohm

• R11

solder 100 K 1 %

Input signal 0/2 … 10 V

• remove front pane
• R10

unsolder 100 Ohm

• R10

solder 26 K1 1 %

• R11

unsolder 0 Ohm

• R11

solder 100 K 1 %

5 Set-up

P

0

P

max

Slide switch

Potentiometer for indication span
Potentiometer for indication span

R10
R11

Offset

0

1. 0. 0. 0.

1.0.0.0

5.3

Adjustment of the zero point and
the measuring range final value

Example: requested indication 000 … 1000

Input signals 0 … 20 mA; 0 … 5 V; 0 … 10 V

• remove front pane and front frame (see section

"Procedure to insert the label")

• set slide switch for zero point correction in position "0“
• switch on the mains
• feed the measuring signal acc. to version 0 … 20 mA or

0 … 5 V / 10 V
-

at 0 mA or 0 V measuring signal, theVEGADIS
indicates „000“

-

at 20 mA or 5 / 10 V measuring signal, the VEGADIS
indicates „1000“

-

the indication can be adjusted in the range of "52.0"
to "174,0" by means of potentiometer P

max.

• adjust requested decimal point with bridge (see section

"adjustment of the decimal point")

Input signals 4 … 20 mA; 1 … 5 V; 2 … 10 V

For the adjustment of the measuring range final value
always the current or voltage difference between initial
and final value must be provided:
at 4 … 20 mA:

20 mA • 4 mA

= 16 mA

at 1 … 5 V:

5 V – 1 V

= 4 V

at 2 … 10 V:

10 V – 2 V

= 8 V

• remove front pane and front frame (see section

"Procedure to insert the label")

• set slide switch for zero point correction in position "0“
• switch on the mains
• acc. to the input signal (difference) provide 16 mA, 4 V

or 8 V

• adjust 100.0 by means of the potentiometer P

max

(measuring range final value)

• set slide switch for zero point correction in position

"Offset"

• acc. to the input signal feed initial value 4 mA, 1 V or

2 V

• adjust 00.0 by means of potentiomter P

0

(zero point

correction)

• adjust requested decimal point with bridge (see section

"adjustment of the decimal point")

Advertising