VEGADIS 171 A

7

5 Set-up

Example: requested indication 10.0 … 90.0

Input signals 0 … 20 mA; 0 … 5 V; 0 … 10 V

• remove front pane and front frame (see section

"Procedure to insert the label")

• switch on the mains
• feed the measuring signal acc. to version 20 mA or

5 V / 10 V

• set slide switch for zero point correction in position "0"
• adjust "80.0" by means of the potentiometer P

max.

(measuring range final value)

• acc. to the input signal feed initial value 0 V or 0 mA
• set slide switch for zero point correction in position

"Offset"

• adjust "10.0" by means of potentiometer P

0

.

Input signals 4 … 20 mA; 1 … 5 V; 2 … 10 V

• remove front pane and front frame (see section

"Procedure to insert the label")

• switch on the mains
• feed the measuring signal (difference) acc. to

version16 mA, 4 V or 8 V

• set slide switch for zero point connection in position "0"
• adjust "80.0" by means of the potentiometer P

max.

(measuring range final value)

• acc. to the input signal feed initial value 4 mA, 1 V or

2 V

• set slide switch for zero point correction in position

"Offset"

• adjust "10.0" by means of potentiometer P

0

.

Adjustment of the decimal point

The decimal point can be adjusted by means of a bridge
(in the example 1000).

Bridge for decimal point

Bridge plugged:
indication 100.0
indication 10.00
indication 1.000

Bridge unplugged:
indication 1000

1 0 0. 0