VEGAPULS 43 – Profibus PA

25

Direct sensor vertically to the product surface

Correct

Incorrect

Ladder

Ladder

Wrong orientation to the product

Weak measuring signals are generated if the
sensor is not directly pointed at the product
surface. Orient the sensor axis perpendicu-
larly to the product surface to achieve opti-
mum measuring results.

3.5 Common installation mistakes

Socket piece too long

If the sensor is mounted in a socket exten-
sion that is too long, strong false echoes
arise which interfere with the measurement.
Make sure that the horn antenna projects out
of the socket piece.

Flange antenna: Correct and unfavourable socket
length

75 %

0 %

100 %

Strong product movements

Strong product movements

Strong turbulence in the vessel, e.g. caused
by powerful stirrers or strong chemical reac-
tions, can seriously interfere with the meas-
urement. A surge or bypass tube (see
illustration) of sufficient size always enables
reliable and problem-free measurement even
if strong turbulence occurs in the vessel,
provided there is no product buildup in the
tube.

Mounting and installation

Correct

Incorrect

Correct

Unfavourable