according to the "Function chart" (max. - max. detection or

overfill protection, min. - min. detection or dry run protection).
We recommend connecting according to the quiescent current

principle (replay contact deenergizes when reaching the

switching point), because the relay takes on the same (safe)

condition if a failure is detected.

Control lamp for indication of the switching condition.

l

green = relay energized

l

red = relay deenergized

l

red (flashing) = failure

6.3 Function chart

The following chart provides an overview of the switching

conditions depending on the adjusted mode and level.

Level

Switching sta-

tus

Control lamp

Mode max.

Overfill protection

5

3

4

(8)

(6) (7)

Relay energized

Green

Mode max.

Overfill protection

5

3

4

(8)

(6) (7)

Relay deener-

gized

red

Mode min.

Dry run protection

5

3

4

(8)

(6) (7)

Relay energized

Green

Mode min.

Dry run protection

5

3

4

(8)

(6) (7)

Relay deener-

gized

red

Signal lamp (4)

VEGAVIB 55 - - double relay (DPDT)

19

Setup

29301

-EN

-070109