3 function chart, Green = relay energized, Red = relay deenergized – VEGA VEGAVIB 55 - double relay (DPDT) User Manual
Page 19: Red (flashing) = failure
according to the "Function chart" (max. - max. detection or
overfill protection, min. - min. detection or dry run protection).
We recommend connecting according to the quiescent current
principle (replay contact deenergizes when reaching the
switching point), because the relay takes on the same (safe)
condition if a failure is detected.
Control lamp for indication of the switching condition.
l
green = relay energized
l
red = relay deenergized
l
red (flashing) = failure
6.3 Function chart
The following chart provides an overview of the switching
conditions depending on the adjusted mode and level.
Level
Switching sta-
tus
Control lamp
Mode max.
Overfill protection
5
3
4
(8)
(6) (7)
Relay energized
Green
Mode max.
Overfill protection
5
3
4
(8)
(6) (7)
Relay deener-
gized
red
Mode min.
Dry run protection
5
3
4
(8)
(6) (7)
Relay energized
Green
Mode min.
Dry run protection
5
3
4
(8)
(6) (7)
Relay deener-
gized
red
Signal lamp (4)
VEGAVIB 55 - - double relay (DPDT)
19