Sensor
current -
Sensor

Level relay
A - overfill
protection

Signal
lamp A -
Overfill
protection

Level relay
B - dry run
protection

Signal
lamp B -
Dry run
protection

Fail safe
relay

Control
lamp

1. Fault sig-
nal
approx. 0.6 s
+

t

A

2)

<

2 mA

currentless

currentless

currentless

2. Empty
signal
(approx.
1.5 s)

approx.
8 mA

energized

currentless

energized

3. Full signal
(approx.
1.5 s)

approx.
16 mA

currentless

energized

energized

4. Return to
current ope-
rating condi-
tion

Note:
When used in measuring chains according to IEC 61508, mode B is
not permitted.

Test passed

l

Interference signal (< 3.6 mA) ≥ 400 ms

l

Uncovered (approx. 8 mA) ≥ 1 s

l

Covered (approx. 16 mA) ≥ 1 s

Test not passed

l

Interference signal (< 3.6 mA) < 400 ms / ≥ 750 ms

l

Uncovered (approx. 8 mA) < 1 s / ≥ 2 s

l

Covered (approx. 16 mA) < 1 s / ≥ 2 s

2)

Starting time of the voltage supply

Test assessment (SPLC)

24

VEGAVIB

62 • - two-wire