VEGA VEGAVIB 62 - two-wire User Manual

Page 30

Advertising
background image

Sensor length (L) - suspension cable FEP
(-40 … +150 °C/-40 … +302 °F)

0.6 … 80 m (1.969 … 262.47 ft)

Output variable

Output

Two-wire output

Suitable signal conditioning instruments

VEGATOR

536Ex, 537Ex, 636Ex

Output signal

-

Mode min.

Vibrating element uncovered: 16 mA ±1 mA,
vibrating element covered: 8 mA ±1 mA

-

Mode max.

Vibrating element uncovered: 8 mA ±1 mA, vibrat-
ing element covered: 16 mA ±1 mA

-

Fault message

<

2.3 mA

Modes (switchable)

min./max.

Switching delay

-

When immersed

0.5 s

-

When laid bare

1 s

Ambient conditions

Ambient temperature on the housing

-40 … +80 °C (-40 … +176 °F)

Storage and transport temperature

-40 … +80 °C (-40 … +176 °F)

Process conditions

Measured variable

Limit level of solids

Process pressure

-1 … 6 bar/-100 … 600 kPa (-14.5 … 87 psig)

Process temperature with PUR suspension
cable

-20 … +80 °C (-4 … +176 °F)

Process temperature with FEP suspension
cable

-40 … +150 °C (-40 … +302 °F)

Product density

-

Standard

>

0.05 g/cm³ (0.002 lbs/in³)

-

adjustable

>

0.02 g/cm³ (0.0007 lbs/in³)

Granular size

no limitation

3)

Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 bar

Cable entry/plug

4)

-

Single chamber housing

l

1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm),
1 x blind stopper M20 x 1.5

or:

3)

max. 20 mm (0.8 in) with product density < 0.05 g/cm³ (0.002 lbs/in³).

4)

Depending on the version M12 x 1, according to ISO 4400, Harting, 7/8" FF.

30

VEGAVIB

62 • - two-wire

9 Supplement

29274

-EN

-120418

Advertising