8 Maintenance and fault rectification

8.1 Maintenance

W

hen used in the correct way, no special maintenance is required in

normal operation.

8.2 Remove interferences

T

he operator of the system is responsible for taken suitable measures

to remove interferences.

A

maximum of reliability is ensured. Nevertheless, faults can occur

during operation. These may be caused by the following, e.g.:

l

S

ensor

l

P

rocess

l

P

ower supply

l

S

ignal processing

T

he first measures to be taken are to check the output signals as well

as to evaluate the error messages via the indicating and adjustment
module. The procedure is described below. Further comprehensive
diagnostics can be carried out on a PC with the software PACTware
and the suitable DTM. In many cases, the causes can be determined
in this way and faults can be rectified.

H

owever, should these measures not be successful, call the VEGA

service hotline in urgent cases under the phone no. +49 1805 858550.

T

he hotline is available to you 7 days a week round-the-clock. Since

we offer this service world-wide, the support is only available in the
E

nglish language. The service is free of charge, only the standard

telephone costs will be charged.

?

W

hen an additional instrument is connected, the H1 segment fails.

l

M

ax. supply current of the segment coupler exceeded

à Measure the current consumption, reduce size of segment

?

M

easured value on the indicating and adjustment module does not

correspond to the value in the PLC

l

T

he menu item "Display - Display value" is not set to "AI-Out"

à Check values and correct, if necessary

?

I

nstrument does not appear during connection setup

l

I

ncorrect termination

à Check termination at the beginning and end points of the bus

and terminate, if necessary, according to the specification

l

I

nstrument not connected to the segment

à Check and correct

Reaction when malfunc-
tions occur

Causes of malfunction

Fault rectification