VEGA VEGASON 65 Foundation Fieldbus User Manual

Page 50

Advertising
background image

Input variable

M

easured value

-

V

ersion A

distance between lower edge of the flange and
product surface

-

version B, C and D

distance between lower edge of the transducer and
product surface

D

ead band

0.8

m (2.624 ft)

M

easuring range

-

L

iquids

up to 45 m (147.6 ft)

-

B

ulk solids

up to 25 m (82.02 ft)

Reference conditions to measuring accuracy (similar to DIN EN 60770-1)

R

eference conditions according to DIN EN 61298-1

-

T

emperature

+18

… +30 °C (+64 … +86 °F)

-

R

elative humidity

45 … 75 %

-

A

ir pressure

860 … 1060

mbar/86 … 106 kPa (12.5 … 15.4 psig)

O

ther reference conditions

-

R

eflector

ideal reflector, e.g. metal plate 2 x 2 m (6.56 x 6.56 ft)

-

F

alse reflections

B

iggest false echo, 20 dB smaller than the useful

echo

Measuring characteristics

U

ltrasonic frequency

18

kHz

I

nterval

> 2

s (dependent on the parameter adjustment)

B

eam angle at 3 dB

A

djustment time

6)

> 3

s (dependent on the parameter adjustment)

Measuring accuracy

R

esolution, general

> 1

mm (0.039 in)

D

eviation

7)

see diagram

6)

T

ime to output the correct level (with max. 10 % deviation) after a sudden

level change.

7)

I

ncl. non-linearity, hysteresis and non-repeatability.

50

VEGASON

65 • F

oundation Fieldbus

10 S

upplement

28794

-EN

-081127

Advertising