VEGA VEGAPULS 61 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus User Manual

Page 38

Advertising
background image

1

Move from the measured value display to the main menu by
pushing [OK].

Basic adjustment

Display
Diagnostics
Service
Info

2

Select the menu item "Basic adjustment" with [->] and confirm with
[OK]

. Now the menu item "Min. adjustment" is displayed.

Min. adjustment

0

.00 %

=

5

.000 m(d)

4.000 m(d)

3

Prepare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.

4

Enter the suitable distance value in m for the empty vessel (e.g.
distance from the sensor to the vessel bottom) corresponding to
the percentage value.

5

Save the settings with [OK] and move to "Max. adjustment" with [-
>

]

.

Proceed as follows:

Max. adjustment

100

.00 %

=

1

.000 m(d)

2.000 m(d)

1

Prepare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.

2

Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the dead band.

3

Save the settings with [OK] and move to "Medium selection" with
[->]

.

Each product has different reflective properties. In addition, there are
various interfering factors which have to be taken into account:
agitated product surfaces and foam generation (with liquids); dust
generation, material cones and echoes from the vessel wall (with
solids). To adapt the sensor to these different conditions, you should
first select "Liquid" or "Solid".

Carrying out max. ad-
justment

Medium selection

38

VEGAPULS

61 • Foundation Fieldbus

6 Set up with the indicating and adjustment module PLICSCOM

28449

-EN

-100426

Advertising