VEGA VEGAPULS 61 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus User Manual

Page 62

Advertising
background image

Diagram, adjustment

The following illustration shows the function of the adjustment.

Secondary_value_1

Calibration

Lowest Point

Calibration

Highest Point

Sensor_value

cal_level_lo

cal_level_hi

Calibration
Lowest Point

Calibration
Highest Point

Sensor reference plane

cal_level_lo [%]

cal_level_hi [%]

Fig. 41: Adjustment VEGAPULS 61

Parameter list
The following list contains the most important parameters and their meaning:

l

primary_value

-

Process value after min/max-adjustment and linearization. Selected as input to AIFB by setting
'C

hannel' = 1. Unit derives from 'Primary_value_unit'

l

primary_value_unit

-

Selected unit code for "primary_value"

l

secondary_value_1

-

Value after min/max-adjustment (level + level offset). Selected as input to AIFB by setting
'C

hannel' = 2. Unit derives from 'Secondary_value_1_unit'

l

secondary_value_1_unit

-

Selected unit code for "secondary_value_1"

l

secondary_value_2

-

Sensor value + sensor offset. Selected as input to AIFB by setting 'Channel' = 3. Unit derives
from 'Secondary_value_2_unit'

62

VEGAPULS

61 • Foundation Fieldbus

10 Supplement

28449

-EN

-100426

Advertising