VEGA VEGAPULS 61 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus User Manual

Page 40

Advertising
background image

A linearization is necessary for all vessels in which the vessel volume
does not increase linearly with the level - e.g. with a horizontal
cylindrical or spherical tank - and the indication or output of the volume
is required. Corresponding linearization curves are preprogrammed for
these vessels. They represent the correlation between the level
percentage and vessel volume. By activating the appropriate curve,
the volume percentage of the vessel is displayed correctly. If the
volume should not be displayed in percent but e.g. in l or kg, a scaling
can be also set in the menu item "Display".

Linearisation curve

linear

Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.

High sockets or vessel installations, such as e. g. struts or agitators as
well as buildup and weld joints on the vessel walls cause interfering
reflections which can impair the measurement. A false echo storage
detects and marks these false echoes, so that they are no longer taken
into account for the level measurement. A false echo memory should
be created with low level so that all potential interfering reflections will
be detected.

Gating out of false signals

Change now?

Proceed as follows:

1

Move from the measured value display to the main menu by
pushing [OK].

2

Select the menu item "Service" with [->] and confirm with [OK].
Now the menu item "False signal suppression" is displayed.

3

Confirm "False signal suppression - Change now" with [OK] and
select in the below menu "Create new". Enter the actual distance
from the sensor to the product surface. All false signals in this area
are detected by the sensor and saved after confirming with [OK].

Note:
Check the distance to the product surface, because if an incorrect (too
large) value is entered, the existing level will be saved as false signal.
The filling level would then no longer be detectable in this area.

Linearisation curve

Gating out of false sig-
nals

40

VEGAPULS

61 • Foundation Fieldbus

6 Set up with the indicating and adjustment module PLICSCOM

28449

-EN

-100426

Advertising