background image

11

4 Mounting

VEGASON 61 • Foundation Fieldbus

28790-EN-130417

1

2

Fig. 3: Minimum distance to the max. level
1 Dead band

2 Reference plane

Information:

If the medium reaches the transducer, buildup can form on it and

cause faulty measurements later on.

1

3

2

100%

0%

Fig. 4: Measuring range (operating range) and max. measuring distance
1 full

2 empty (max. measuring distance)

3 Measuring range

Gauge pressure in the vessel does not influence VEGASON 61. Low

pressure or vacuum does, however, damp the ultrasonic pulses. This

influences the measuring result, particularly if the level is very low.

With pressures under -0.2 bar (-20 kPa) you should use a different

measuring principle, e.g. radar or guided microwave.

4.2 Mounting instructions

Screw VEGASON 61 into the mounting socket with an appropriate

spanner applied to the hexagon of the process fitting. Max. torque see

chapter "Technical data".

Warning:

The housing must not be used to screw the instrument in! Applying

tightening force can damage internal parts of the housing.

Pressure/Vacuum

Screwing in