VEGA VEGASON 61 Foundation Fieldbus User Manual

Page 42

Advertising
background image

42

10 Supplement

VEGASON 61 • Foundation Fieldbus

28790-EN-130417

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Other reference conditions

Ʋ Reflector

ideal reflector, e.g. metal plate 2 x 2 m (6.56 x 6.56 ft)

Ʋ False reflections

Biggest false signal, 20 dB smaller than the useful signal

Measuring characteristics
Ultrasonic frequency

70 kHz

Interval

> 2 s (dependent on the parameter adjustment)

Abstrahlwinkel at -3 dB

11°

Step response or adjustment time

6)

> 3 s (dependent on the parameter adjustment)

Measuring accuracy
Resolution, general

> 1 mm (0.039 in)

Deviation

7)

see diagram

5 m (16.404 ft)

4 m (13.123 ft)

3 m (9.843 ft)

2 m (6.562 ft)

1 m (3.28 ft)

10 mm (0.394 in)

4 mm (0.157 in)

-10 mm (-0.394 in)

-4 mm (-0.157 in)

Fig. 28: Deviation VEGASON 61

Influence of the ambient temperature to the sensor electronics

8)

Average temperature coefficient of the

zero signal (temperature error)

0.06 %/10 K

Ambient conditions
Ambient, storage and transport tempera-

ture

-40 … +80 °C (-40 … +176 °F)

Process conditions
Process pressure

-20 … 200 kPa/-0.2 … 2 bar (-2.9 … 29 psig)

Process temperature (transducer tem-

perature)

-40 … +80 °C (-40 … +176 °F)

Vibration resistance

mechanical vibrations with 4 g and 5 … 100 Hz

9)

6)

Time to output the correct level (with max. 10 % deviation) after a sudden level change.

7)

Incl. non-linearity, hysteresis and non-repeatability.

8)

Relating to the nominal measuring range.

9)

Tested according to the guidelines of German Lloyd, GL directive 2.

Advertising