3 exchange of the electronics – VEGA VEGAVIB 67 - two-wire User Manual

Page 28

Advertising
background image

à

Check if there is buildup on the vibrating element, and if

so, remove it.

l

Unfavourable installation location

à

Mount the instrument at a location in the vessel where

no dead zones or mounds can form.

à

Check if the vibrating element is covered by buildup on

the socket.

l

Wrong mode selected

à

Set the mode switch on VEGAVIB 67 to "max". Set the

correct mode on the signal conditioning instrument (A:

overfill protection; B: dry run protection).

?

Signal lamp flashes red

l

Electronics has detected a failure

à

Exchange instrument or return it for repair

7.3 Exchange of the electronics

In general, all oscillators of series VB60 can be interchanged. If

you want to use an oscillator with a different signal output, you

can download the corresponding operating instructions man-

ual from our homepage under Downloads.

With EEx d instruments, the housing cover must only be

opened if there is no explosive atmosphere.

Proceed as follows:
1 Switch off power supply
2 Unscrew the housing cover
3 Lift the opening levers of the terminals with a screwdriver
4 Pull the connection cables out of the terminals
5 Loosen the two screws with a screw driver (Torx size T10

or slot 4)

Maintenance and fault rectification

28

VEGAVIB 67 - with two-wire output

29298

-EN
-060508

Advertising