6 set up, 1 general – VEGA VEGAVIB 66 - two-wire User Manual
Page 20
6 Set up
6.1 General
The numbers in brackets refer to the following illustrations.
On the electronics module you will find the following indicating
and adjustment elements:
l
Potentiometer for switching point adaptation (1)
l
DIL switch for mode adjustment - min./max. (2)
l
Signal lamp (5)
Note:
As a rule, always set the mode with mode switch (2) before
starting the setup of VEGAVIB 66 . If the instrument is used in
conjunction with a signal conditioning instrument, always set
the mode switch (2) on VEGAVIB 66 to max. mode.
The mode is selected on the signal conditioning instrument
with the mode switch.
The switching output will change if you set one of the two mode
switches afterwards. This could possibly trigger other con-
nected instruments or devices.
Function/Configuration
20
VEGAVIB 66 - with two-wire output
Set up
29292
-EN
-060508