VEGA VEGAVIB 66 - two-wire User Manual

Page 26

Advertising
background image

Sensor

current

VEGAVIB

Level re-

lay VEGA-

TOR A -

Overfill

protection

Level re-

lay VEGA-

TOR B -

Dry run

protection

LED

VEGATOR

A - Overfill

protection

LED

VEGATOR

B - Dry

run pro-

tection

Fail safe

relay

VEGATOR

LED

1. Fault signal

(approx. 3 s)

<2 mA

currentless currentless

currentless

2. Empty signal

(approx. 1.5 s)

approx.

8 mA

energized

currentless

energized

3. Full signal

(approx. 1.5 s)

approx.

16 mA

currentless energized

energized

4. Return to the actual

operating condition

Note:

When used in measuring chains according to IEC 61508,

mode B is not permitted.

With the stated current values you can carry out the function

test directly via a safety SPLC or a process control system.

26

VEGAVIB 66 - with two-wire output

Set up

29292

-EN
-060508