10.1 Technical data

General data
Materials, wetted parts

Ʋ Process fitting, transducer

PVDF

Ʋ Seal between transducer and process

fitting

EPDM, FKM (Viton)

Materials, non-wetted parts

Ʋ Housing

Plastic PBT (polyester), Alu die-casting powder-coated,

316L

Ʋ Seal between housing and housing

cover

NBR (stainless steel housing), silicone (Alu/plastic hous-

ing)

Ʋ Inspection window in housing cover

Polycarbonate

Ʋ Ground terminal

316Ti/316L

Weight

1.8 … 4 kg (4 … 8.8 lbs), depending on the process

fitting and housing

Max. torque mounting boss

25 Nm

Output variable
Output signal

4 … 20 mA/HART

HART output values

Ʋ HART value (Primary Value)

Distance to the level

Ʋ HART value (Secondary Value)

Temperature

Ʋ HART value (3rd Value)

Distance to the level - scaled

Signal resolution

1.6 µA

Failure signal current output (adjustable) mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA
Current limitation

22 mA

Load

see load diagram under Power supply

Damping (63 % of the input variable)

0 … 999 s, adjustable

Met NAMUR recommendation

NE 43

Input variable
Measured variable

distance between lower edge of the transducer and

product surface

Measuring range

Ʋ Liquids

up to 5 m (16.4 ft)

Ʋ Bulk solids

up to 2 m (6.562 ft)

Dead band

0.25 m (0.82 ft)

Reference conditions to measuring accuracy (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %