VEGA VEGASON 61 4 … 20 mA_HART - two-wire User Manual
Page 8
8
3 Product description
VEGASON 61 • 4 … 20 mA/HART - two-wire
28775-EN-130417
•
Article numbers, documentation
•
Technical data: For example approvals, process temperature,
process fitting/material, signal output, power supply, protection
•
SIL identification (with SIL rating ex works)
With the serial number, you can access the delivery data of the instru-
ment via www.vega.com, "VEGA Tools" and "serial number search".
In addition to the type label outside, you can also find the serial num-
ber on the inside of the instrument.
3.2 Principle of operation
VEGASON 61 is an ultrasonic sensor for continuous level measure-
ment. It is suitable for liquids and solids in virtually all industries,
particularly in the water and waste water industry.
The transducer of the ultrasonic sensor transmits short ultrasonic
pulses to the measured product. These pulses are reflected by
product surface and received back by the transducer as echoes.
The running time of the ultrasonic pulses from emission to reception
is proportional to the distance and hence the level. The determined
level is converted into an appropriate output signal and outputted as
measured value.
4 … 20 mA/HART two-wire electronics for voltage supply and meas-
ured value transmission on the same cable.
The supply voltage range can differ depending on the instrument
version.
The data for power supply are specified in chapter "Technical data".
The optional background lighting of the display and adjustment
module is powered by the sensor. A certain level of operating voltage
is required for this. You can find the exact voltage specifications in
chapter "Technical data".
The optional heating requires its own operating voltage. You can find
details in the supplementary instructions manual "Heating for display
and adjustment module".
This function is generally not available for approved instruments.
3.3 Operation
The instrument can be adjusted with the following adjustment media:
•
With the display and adjustment module
•
with the suitable VEGA DTM in conjunction with an adjustment
software according to the FDT/DTM standard, e.g. PACTware and
PC
•
with manufacturer-specific adjustment programs AMS™ or PDM
•
With a HART handheld
Application area
Functional principle
Voltage supply