VEGA VEGACAP 65 - contactless electronic switch User Manual

Page 17

Advertising
background image

17

5 Connecting to power supply

VEGACAP 65 • - contactless electronic switch

30017-EN-130916

4

5

6

3

2

1

Fig. 10: Electronics and connection compartment
1 Potentiometer for switching point adaptation

2 DIL switch for measuring range selection

3 DIL switch for mode adjustment

4 Ground terminal

5 Connection terminals

6 Control lamp

We recommend connecting VEGACAP 65 in such a way that the

switching circuit is open when there is a level signal, line break or

failure (safe condition).
The contactless electronic switch is always shown in non-operative

condition.

Warning:

The instrument must not be operated without an intermediately

connected load, because the electronics would be destroyed if con-

nected directly to the mains. It is not suitable for connection to low

voltage PLC inputs.
Examples for typical applications:

Load resistance at 24 V DC: 88 … 1800 Ω

Rated power, relay 253 V AC: > 2.5 VA

Rated power, relay 24 V AC: > 0.5 VA

For direct control of relays, contactors, magnet valves, warning lights,

horns etc.
Domestic current is temporarily lowered below 1 mA after switching

off the load so that contactors, whose holding current is lower than

the constant domestic current of the electronics, are reliably switched

off.

Electronics and connec-

tion compartment

Wiring plan

Advertising