7 Maintenance and fault rectification

VEGACAP 65 • - contactless electronic switch

30017-EN-130916

2

1

Fig. 31: Compensation key
1 Measuring range selection switch (compensation key)

2 Control lamp

16. Keep the measuring range selection switch (1) pushed until the

control lamp (2) flashes green.

17. Carry out the adjustment again. See chapter "Set-up, adjustment

elements".

18. Screw the housing cover back on
The electronics exchange is now finished.

7.4 Shortening of the probe

The probe can be shortened by any amount.
1. Loosen the two pins on the gravity weight (hexagon) and remove

the pins.

2. Pull the cable out of the gravity weight.
3. To avoid splicing of the steel cable, tin the cable before shortening

with a soldering iron and tighten the wire.

4. Shorten the cable with a cut-off wheel or metal saw at the lower

end. Make sure the length is correct before shortening.

70 mm (2.76"

)

200 mm

(7.87"

)

Fig. 32: Take the gravity weight into account and shorten the cable respectively