VEGA VEGAPULS 66 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus User Manual

Page 51

Advertising
background image

Reference conditions to measuring accuracy (similar to DIN EN 60770-1)

Reference conditions according to DIN EN 61298-1

-

Temperature

+18

… +30 °C (+64 … +86 °F)

-

Relative humidity

45 … 75 %

-

Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Other reference conditions

-

Reflector

ideal reflector, e.g. metal plate 2 x 2 m

-

False reflections

Biggest false echo, 20 dB smaller than the useful
echo

Characteristics and performance data

Frequency

C-band (6 GHz technology)

Beam angle 3 dB, depending on the antenna system

-

without horn antenna

38°

-

ø

75 mm (2.953 in)

38°

-

ø

96 mm (3.78 in)

30°

-

ø

146 mm (5.748 in)

20°

-

ø

196 mm (7.717 in)

17°

-

ø

242 mm (9.528 in)

14°

Step response or adjustment time

5)

> 1

s (dependent on the parameter setting)

Max. level change

adjustable up to 1 m/min. (dependent on the
parameter adjustment)

Max. emitted HF power of the antenna system

-

Pulse peak power approx.

0.1 mW

-

Pulse duration

< 2

ns

-

SAR value

6)

0.471 mW/kg

Measuring accuracy

Resolution, general

max. 1 mm (0.039 in)

Deviation

7)

see diagrams

5)

Time to output the correct level (with max. 10 % deviation) after a sudden
level change.

6)

at the aperture of a horn antenna with ø 150 mm

7)

Incl. non-linearity, hysteresis and non-repeatability.

VEGAPULS

66 • Foundation Fieldbus

51

10 Supplement

28453

-EN

-090305

Advertising