4 Mounting
VEGASON 62 • Profibus PA
28785-EN-130417
ca. 10 mm
Fig. 7: Recommended socket mounting
If the reflective properties of the medium are good, you can mount
VEGASON 62 on sockets which are higher than the length of the
transducer. You will find recommended values for socket heights in the
following illustration. The socket end should be smooth and burr-free,
if possible also rounded. Carry out a false echo storage.
d
d
h
100 mm/4"
150 mm/6"
200 mm/8"
300 mm/12"
400 mm/16"
500 mm/20"
h
Fig. 8: Deviating socket dimensions
Align the sensor in liquids as vertical as possible to the product sur-
face to achieve an optimum measurement result.
Fig. 9: Alignment in liquids
To reduce the min. distance to the medium, you can also mount VE-
GASON 62 with a beam deflector. By doing this, it is possible to fill the
vessel nearly to maximum. Such an arrangement is suitable primarily
for open vessels such as e.g. overflow basins.
Sensor orientation