8 maintenance and fault rectification, 1 maintenance, 2 rectify faults – VEGA VEGASON 62 Profibus PA User Manual

Page 36

Advertising
background image

36

8 Maintenance and fault rectification

VEGASON 62 • Profibus PA

28785-EN-130417

8 Maintenance and fault rectification

8.1 Maintenance

If the instrument is used properly, no special maintenance is required

in normal operation.

8.2 Rectify faults

The operator of the system is responsible for taking suitable meas-

ures to rectify faults.

VEGASON 62 offers maximum reliability. Nevertheless, faults can oc-

cur during operation. These may be caused by the following, e.g.:

Sensor

Process

Voltage supply

Signal processing

The first measures to be taken are to check the output signals as well

as to evaluate the error messages via the display and adjustment

module. The procedure is described below. Further comprehensive

diagnostics can be carried out on a PC with the software PACTware

and the suitable DTM. In many cases, the causes can be determined

and the faults rectified this way.

Should these measures not be successful, please call in urgent cases

the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is available to you 7 days a week round-the-clock. Since

we offer this service world-wide, the support is only available in the

English language. The service is free of charge, only the standard

telephone costs will be charged.

The following table describes possible errors and helps to remove

them:

Error

Cause

Rectification

When an addi-

tional instrument

is connected, the

segment fails.

Max. supply

current of the seg-

ment coupler

exceeded

Measure the current consumption, re-

duce size of segment

Wrong pres-

entation of the

measured value in

Simatic S5

Simatic S5 cannot

interpret the num-

ber format IEEE

of the measured

value

Insert converting component from Sie-

mens

In Simatic S7 the

measured value

is always present-

ed as 0

Only four bytes

are consistently

loaded in the PLC

Use function component SFC 14 to

load 5 bytes consistently

Reaction when malfunc-

tions occur

Failure reasons

Fault rectification