3 instrument repair – VEGA VEGASWING 63 Lock fitting ARV-SG63.2 - pressure range: -1…16 bar User Manual

Page 11

Advertising
background image

11 Clean the connection tube of the sensor and the surfaces

of the clamp (1) as well as the pressure screw (11)
carefully and remove grease, oil and dirt. Insert the sensor
into the lock fitting. Slide the tube into the requested
position and hold it

12 Make sure that the sensor is in the correct position (height).

The height adjustment of the sensor determines also the
switching point

13 Tighten the pressure screw (11) with a torque 70 ±10 Nm

(51 ±7 lbf ft)

14 Continue to turn the pressure screw (11) clockwise until the

hexagon surfaces of the pressure screw (11) and the
mounting boss (7) correspond (max. 1/6 turn)

15 Tighten the terminal screws (3) alternately. Make sure that

the gap between clamp and pressure screw is in parallel.
Tighten the terminal screws with a defined torque.

Corresponding torques: see chapter "Technical data".

Hence the clamp (1) is pressed against the tube and fixes
the tube of the sensor in this position

16 Fasten the locking angle (4) with the hold screw (6) and the

spring ring (5) laterally on the pressure screw (11)

Hence the pressure screw and the terminal screw are
secured against unintentional loosening

5

.3 Instrument repair

If a repair should be necessary, please ask the agency serving
you for the address of the return shipment.

Lock fitting ARV-SG63.2 • - pressure range: -1 … 16 bar

11