VEGA VEGAPULS 62 (≥ 2.0.0 - ≤ 3.8) standpipe ver. 4 … 20 mA_HART two-wire User Manual

Page 46

Advertising
background image

Input variable

M

easured value

D

istance between process fitting (seal surface

hexagon or lower edge of flange) of the sensor and
product surface

M

in. distance

0

mm

M

easuring range

up to 5.85 m (19.19 ft)

3)

Reference conditions to measuring accuracy (similar to DIN EN 60770-1)

R

eference conditions according to DIN EN 61298-1

-

T

emperature

+

18 … +30 °C (+64 … +86 °F)

-

R

elative humidity

45 … 75 %

-

A

ir pressure

860 … 1060

mbar/86 … 106 kPa (12.5 … 15.4 psig)

O

ther reference conditions

-

R

eflector

ideal reflector, e.g. metal plate 2 x 2 m

-

F

alse reflections

B

iggest false echo, 20 dB smaller than the useful

echo

Characteristics and performance data

F

requency

K-

band (26 GHz technology)

M

eas. interval approx.

1

s

S

tep response or adjustment time

4)

<

1

s (dependent on the parameter settings)

M

ax. level change

A

djustable up to 1 m/min. (dependent on the

parameter adjustment)

M

ax. emitted HF power of the antenna system

-

P

ulse peak power

<

2

mW

-

P

ulse duration

<

2

ns

-

A

verage power

<

5 µW

-

A

verage power with 1 m distance

<

200

nW/cm

2

M

ax. emitted HF power of the antenna system - Version with increased sensitivity

-

P

ulse peak power

<

10

mW

-

P

ulse duration

<

2

ns

-

A

verage power

<

25 µW

-

A

verage power with 1 m distance

<

1 µW/

cm

2

Measuring accuracy

R

esolution, general

<

1

mm (0.039 in)

3)

A

ccording to the respective standpipe length.

4)

T

ime to output the correct level (with max. 10 % deviation) after a sudden

level change.

46

VEGAPULS

62

standpipe version • 4 … 20 mA/HART two-wire

10 S

upplement

28737

-EN

-090305

Advertising