VEGA VEGAPULS 62 (≥ 2.0.0 - ≤ 3.8) standpipe ver. 4 … 20 mA_HART two-wire User Manual

Page 47

Advertising
background image

D

eviation

5)

see diagram

0,5 m (1.6 ft)

5,85 m (19.19 ft)

10 mm (0.394 in)

3 mm (0.116 in)

- 3 mm (- 0.116 in)

- 10 mm (- 0.394 in)

0

Fig. 24: Deviation VEGAPULS 62 standpipe

Influence of the ambient temperature to the sensor electronics

6)

A

verage temperature coefficient of the zero

signal (temperature error)

0.03 %/10 K

Influence of the superimposed gas and pressure to the accuracy
T

he spreading speed of the radar impulses in gas or vapour above the product is reduced by high

pressures. This effect depends on the superimposed gas or vapour and increases with low
temperatures. The following chart shows the deviation caused by some typical gases or vapours.
T

he stated values refer to the distance. Positive values mean that the measured distance is too

high, negative values that the measured distance is too small.

Gas phase

Temperature

1 bar/14.5 psig

10 bar/145 psig

50 bar/725 psig

A

ir/Nitrogen

20 °C/68 °F

0.00 %

0.22 %

1.2 %

A

ir/Nitrogen

200 °C/392 °F

0.00 %

0.13 %

0.74 %

H

ydrogen

20 °C/68 °F

-0.01 %

0.10 %

0.61 %

H

ydrogen

200 °C/392 °F

-0.02 %

0.05 %

0.37 %

W

ater (saturated

steam)

100 °C/212 °F

0.20 %

-

-

W

ater (saturated

steam)

180 °C/356 °F

-

2.1 %

-

Ambient conditions

A

mbient, storage and transport temperature

-40 … +80 °C (-40 … +176 °F)

5)

I

ncl. non-linearity, hysteresis and non-repeatability.

6)

R

elating to the nominal measuring range, in the temperature range

-40 … +80 °C .

VEGAPULS

62

standpipe version • 4 … 20 mA/HART two-wire

47

10 S

upplement

28737

-EN

-090305