VEGA VEGAPULS 62 (≥ 2.0.0 - ≤ 3.8) standpipe ver. Foundation Fieldbus User Manual

Page 46

Advertising
background image

Input variable

Measured value

Distance between process fitting (seal surface
hexagon or lower edge of flange) of the sensor and
product surface

Min. distance

0 mm

Measuring range

up to 5.85 m (19.19 ft)

6)

Reference conditions to measuring accuracy (similar to DIN EN 60770-1)

Reference conditions according to DIN EN 61298-1

-

Temperature

+18

… +30 °C (+64 … +86 °F)

-

Relative humidity

45 … 75 %

-

Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Other reference conditions

-

Reflector

ideal reflector, e.g. metal plate 2 x 2 m

-

False reflections

Biggest false echo, 20 dB smaller than the useful
echo

Characteristics and performance data

Frequency

K-band (26 GHz technology)

Meas. interval approx.

1 s

Step response or adjustment time

7)

< 1

s (dependent on the parameter settings)

Max. level change

Adjustable up to 1 m/min. (dependent on the
parameter adjustment)

Max. emitted HF power of the antenna system

-

Pulse peak power

< 2

mW

-

Pulse duration

< 2

ns

-

Average power

< 5 µW

-

Average power with 1 m distance

< 200

nW/cm

2

Max. emitted HF power of the antenna system - Version with increased sensitivity

-

Pulse peak power

< 10

mW

-

Pulse duration

< 2

ns

-

Average power

< 25 µW

-

Average power with 1 m distance

< 1 µW/

cm

2

Measuring accuracy

Resolution, general

< 1

mm (0.039 in)

6)

According to the respective standpipe length.

7)

Time to output the correct level (with max. 10 % deviation) after a sudden
level change.

46

VEGAPULS

62 standpipe version • Foundation Fieldbus

10 Supplement

28740

-EN

-090305