6.4 Recurring test and function test (SIL, WHG)

The VEGASWING 61 is qualified for use in measuring chains of level

SIL2 according to IEC 61508 (redundant, level SIL3) and is approved

according to WHG.

The implementation of the recurring test according to WHG is stipu-

lated in the general type approval, item 8.
Take note of these higher-ranking approvals if VEGASWING 61 Ex is

used as part of an overfill protection system according to WHG.
The following instrument combinations meet the requirements ac-

cording to WHG:
VEGASWING 61 Ex with

Oscillator SWE60Z EX

Signal conditioning instrument VEGATOR 536Ex, 537Ex and

636Ex, VEGALOG or SPLC (safety-oriented PLC)

The measuring system can be used for level detection of liquids and

meets the special requirements of safety technology.
This is possible up to SIL2 in a single channel architecture (1oo1D),

and up to SIL3 in a multiple channel, redundant architecture.
The following instrument combinations meet the requirements ac-

cording to SIL:
VEGASWING 61 Ex with

Oscillator SWE60Z EX

Signal conditioning instrument VEGATOR 636Ex or SPLC (safety-

oriented PLC)