VEGA VEGASON 61 Profibus PA User Manual

Page 30

Advertising
background image

30

6 Set up with the display and adjustment module PLICSCOM

VEGASON 61 • Profibus PA

28784-EN-130417

reduced, false reflections by agitators or vessel installations can

cause measured value fluctuations. A false echo memory is thus

recommended.

This function enables reading out parameter adjustment data as well

as writing parameter adjustment data into the sensor via the display

and adjustment module. A description of the function is available in

the operating instructions manual "Display and adjustment module".
The following data are read out or written with this function:

Measured value presentation

Adjustment

Medium

Vessel form

Damping

Linearization curve

Sensor-TAG

Displayed value

Scaling unit (Out-Scale unit)

Positions after the decimal point (scaled)

Scaling PA/Out-Scale 4 values

Unit of measurement

Language

The following safety-relevant data are not read out or written:

Sensor address

PIN

Copy sensor data

Copy sensor data?

Basic adjustment

If the "Reset" is carried out, the sensor resets the values of the follow-

ing menu items to the reset values (see chart):

2)

Menu section

Function

Reset value

Basic settings

Max. adjustment

0 m(d)

Min. adjustment

Meas. range end in

m(d)

3)

Medium

Liquid

Vessel form

not known

Damping

0 s

Linearization

Linear

Channel

PV lin. %

Sensor-TAG

Sensor

Display

Displayed value

PA-Out

Copy sensor data

Reset

2)

Sensor-specific basic adjustment.

3)

Depending on the sensor type, see chapter "Technical data".