VEGA VEGAPULS 68 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus User Manual

Page 57

Advertising
background image

Influence of the ambient temperature to the sensor electronics

7)

Average temperature coefficient of the zero
signal (temperature error)

0.03 %/10 K

Ambient conditions

Ambient, storage and transport temperature

-40 … +80 °C (-40 … +176 °F)

Process conditions

Process temperature (measured on the process fitting), depending on seal and antenna system

-

FKM (Viton)

-40 … +130 °C (-40 … +266 °F)

-

FFKM (Kalrez 6375)

-20 … +130 °C (-4 … +266 °F)

-

FFKM (Viton) with temperature adapter

-40 … +200 °C (-40 … +392 °F)

-

FFKM (Kalrez 6375) with temperature
adapter

-20 … +200 °C (-4 … +392 °F)

-

FFKM (Kalrez 2035, 6230)

-15 … +130 °C (+5 … +266 °F)

-

FFKM (Kalrez 2035, 6230) with temper-
ature adapter

-15 … +200 °C (+5 … +392 °F)

For the vessel pressure, you also have to note the specifications on the type label. Always the
lowest value is applicable.

Vessel pressure - horn antenna

-

without swivelling holder

-1 … 40 bar/-100 … 4000 kPa (-14.5 … 580 psig)

-

with swivelling holder

-1 … 1 bar/-100 … 100 kPa (-14.5 … 14.5 psig) not
sealing

Vessel pressure - parabolic antenna

-

without swivelling holder

-1 … 6 bar/-100 … 600 kPa (-14.5 … 87 psig)

-

with swivelling holder

-1 … 1 bar/-100 … 100 kPa (-14.5 … 14.5 psig) not
sealing

Vessel pressure relating to the flange nom-
inal stage

see supplementary instructions manual "Flanges
according to DIN-EN-ASME-JIS
"

Vibration resistance

8)

-

Horn antenna

mechanical vibrations with 4 g and 5 … 100 Hz

-

Parabolic antenna

mechanical vibrations with 1 g and 5 … 100 Hz

Data on rinsing air connection

Pressure

< 6

bar (87.02 psi)

Air quantity see diagram

7)

Relating to the nominal measuring range, in the temperature range
-40 … +80 °C .

8)

Tested according to the regulations of German Lloyd, GL directive 2.

VEGAPULS

68 • Foundation Fieldbus

57

10 Supplement

29264

-EN

-090305