6 set up, 1 general information, 2 adjustment elements – VEGA VEGAVIB 63 - NAMUR User Manual

Page 19: 6set up

Advertising
background image

6

Set up

6

.1 General information

The figures in brackets refer to the following illustrations.

On the electronics module you will find the following indicating and
adjustment elements:

l

Potentiometer for adaptation to the product density (1)

l

DIL switch for mode adjustment - min./max. (2)

l

Simulation key (3)

l

Signal lamp (6)

6

.2 Adjustment elements

4

5

6

3

1

2

Simulation

NAMUR IEC 60947-5-6

VB60N

Fig. 12: Electronics and connection compartment - NAMUR output

1

Potentiometer for switching point adaptation

2

DIL switch for characteristics reversal

3

Simulation key

4

Ground terminal

5

Connection terminals

6

Control lamp

With the potentiometer you can adapt the switching point to the solid. It
is already preset and must only be modified in special cases.

As a default setting, the potentiometer of VEGAVIB 63 is set to the
complete right position (> 0.3 g/cm³/0.011 lbs/in³). In very light solids
you have to turn the potentiometer to the complete left position
(0.02 … 0.1 g/cm³ or 0.0007 … 0.0036 lbs/in³). By doing this,

Function/Configuration

Electronics and connec-
tion compartment

Switching point adapta-
tion (1)

VEGAVIB

63 • - NAMUR

19

6 Set up

31217

-

EN

-120418

Advertising