4 instrument repair – VEGA VEGAVIB 63 - NAMUR User Manual

Page 26

Advertising
background image

2

1

Fig. 29: Loosening the holding screws

1

Electronics module

2

Screws (2 pcs.)

6

Pull out the old electronics module

7

Compare the new electronics module with the old one. The type
label of the electronics module must correspond to that of the old
electronics module. This applies particularly to instruments used in
hazardous areas.

8

Compare the settings of the two electronics modules. Set the
adjustment elements of the new electronics module to the same
setting of the old one.

Information:
Make sure that the housing is not rotated during the electronics
exchange. Otherwise the plug may be in a different position later.

9

Insert the electronics module carefully. Make sure that the plug is
in the correct position.

10 Screw in and tighten the two holding screws with a screwdriver

(Torx size T10 or Phillips 4)

11 Insert the wire ends into the open terminals according to the wiring

plan

12 Press down the opening levers of the terminals, you will hear the

terminal spring closing

13 Check the hold of the wires in the terminals by lightly pulling on

them

14 Check cable gland on tightness. The seal ring must completely

encircle the cable.

15 Screw the housing cover back on

The electronics exchange is now finished.

7

.4 Instrument repair

If a repair is necessary, please proceed as follows:

26

VEGAVIB

63 • - NAMUR

7 Maintenance and fault rectification

31217

-EN

-120418

Advertising