Wire resistance

<

0.036 Ω/m (0.011 Ω/ft)

-

Tensile strength

<

1200 N (270 lbf)

-

Standard length

5 m (16.4 ft)

-

Max. length

1000 m (3280 ft)

-

Min. bending radius

25 mm (0.984 in) with 25 °C (77 °F)

-

Diameter approx.

8 mm (0.315 in)

-

Colour - standard PE

Black

-

Colour - standard PUR

Blue

-

Colour - Ex-version

Blue

Adjustment elements

Mode switch

-

Min.

rising characteristic curve (High current when
immersed)

-

Max.

falling characteristics (Low current when immersed)

Potentiometer for switching point adaptation

0.02 … 0.1 g/cm³ (0.0007 … 0.036 lbs/in³)

Simulation key

simulation of a line break between sensor and
processing unit

Voltage supply

Operating voltage (characteristics according
to standard)

for connection to an amplifier according to NAMUR
IEC

60947-5-6, approx. 8.2 V

Off-load voltage

U

0

approx. 8.2 V

Shortcircuit current

I

U

approx. 8.2 mA

Electrical protective measures

Protection rating

-

Plastic housing

IP

66/IP 67

-

Aluminium and stainless steel standard

IP

66/IP 68 (0.2 bar)

3)

-

Aluminium and stainless housing (op-
tionally available)

IP

66/IP 68 (1 bar)

Overvoltage category

III

Protection class

II

Approvals

Instruments with approvals can have different technical data depending on the version.

That's why the associated approval documents have to be noted with these instruments. They are
part of the delivery or can be downloaded under www.vega.com via "VEGA Tools" and "serial
number search
" as well as via "Downloads" and "Approvals".

3)

A suitable cable is the prerequisite for maintaining the protection rating.