VEGA VEGAFLEX 67 (-40…+150°C PFA insulated) Foundation Fieldbus User Manual

Page 45

Advertising
background image

L

0

15 mm

(0.591

"

)

-15 mm

(-0.591

"

)

10 mm

(0.394

")

-10 mm

(-0.394

")

0,35 m

(13.78

")

0,2 m

(7.874

"

)

0,2 m

(7.874

")

0,05 m

(1.969

")

1

1

Fig. 21: Deviation VEGAFLEX 67 in cable version

1

Dead zone - no measurement possible in this area

L

Probe length

Influence of the ambient temperature to the sensor electronics
Temperature drift

0.03 %/10 K relating to the max. measuring range
or max. 0.3 %

Temperature drift - Digital output

3 mm/10 K relating to the max. measuring range or
max. 10 mm

Ambient conditions

Ambient, storage and transport temperature

-40 … +80 °C (-40 … +176 °F)

Process conditions

Process pressure

-

Flange version ≤ 2"/DN 50

-0.5 … +16 bar/-50 … +1600 kPa (-7.3 … +232 psig),
depending on the process fitting

-

Flange version > 2"/DN 50

-0.2 … +16 bar/-20 … +1600 kPa (-2.9 … +232 psig),
depending on the process fitting

Process temperature (flange temperature)

-40 … +150 °C (-40 … +302 °F)

The measurement error from the process condi-
tions is in the specified pressure and temperature
range of below 1 %.

VEGAFLEX

67 • Foundation Fieldbus

45

10 Supplement

32306

-

EN

-120329

Advertising