Fig. 21: Deviation VEGAFLEX 67 in cable version
1
Dead zone - no measurement possible in this area
L
Probe length
Influence of the ambient temperature to the sensor electronics
Temperature drift
0.03 %/10 K relating to the max. measuring range
or max. 0.3 %
Temperature drift - Digital output
3 mm/10 K relating to the max. measuring range or
max. 10 mm
Ambient conditions
Ambient, storage and transport temperature
-40 … +80 °C (-40 … +176 °F)
Process conditions
Process pressure
-
Flange version ≤ 2"/DN 50
-0.5 … +16 bar/-50 … +1600 kPa (-7.3 … +232 psig),
depending on the process fitting
-
Flange version > 2"/DN 50
-0.2 … +16 bar/-20 … +1600 kPa (-2.9 … +232 psig),
depending on the process fitting
Process temperature (flange temperature)
-40 … +150 °C (-40 … +302 °F)
The measurement error from the process condi-
tions is in the specified pressure and temperature
range of below 1 %.